HIOKI 3157-01 AC GROUNDING HiTESTER New in box.
Protective ground tester indispensable for standard certification
Designed to measure whether the metal enclosure of electrical equipment is connected to the ground terminal at sufficiently low resistance levels. It also can be used to evaluate the grounding conditions of large-scale electrical installations. Measurement is carried out by using a high current according to the specifications of the measurement object, and determining the voltage drop at the measurement point. Reference values are as set out in the various safety standards. The 3157-01 can carry out measurements in accordance with the stipulations of multiple standards.
Low resistance, AC 4-terminal method
Current generator principle: PWM constant current control
Current setting range: 3.0 A to 31.0 A (0.1 A resolution), into 0.1 Ohm load
Maximum output power: 130 VA*1 (at output terminals)
*1 Subject to derating according to ambient temperature (80 % at 40 ?‹C)
Frequency: 50 Hz or 60 Hz sine wave
Soft start function: Apply current only after checking load connection
Resistance measurement: 0 to 1.800 Ohm (0.001 Ohm resolution)
Accuracy: ±2 % rdg. ±4 dgt. (after zero-adjust)
Current monitoring range: 0 to 35.0 A AC (0.1 A resolution)
Monitoring cycle: 2 times/second
Timer setting: Counts down time after start until preset time, or shows elapsed time after start
Setting range: 0.5 to 999 second
Comparator: Pass/Fail evaluation using preset upper/lower limit, I/O output
Memory function: max. 20 settings (with save/load)
Fluorescent tube digital display
100 to 120 V, 200 to 240 V AC (auto-switching), 50/60 Hz
320 mm(12.60 in)W × 90 mm(3.54 in)H × 263 mm(10.35 in)D, 7 kg (246.9 oz)